INS. PIERCING CONN. 35-35MM2

Part No. IPC35/35

  • Designed to tap off low voltage XLPE insulated ABC cables using a unique insulation piercing technique
  • Suitable for all weather applications and corrosion resistant
  • Connections can be made fully live in minutes
  • Suitable for Aluminium and Copper
  • Scan QR Code - store on your mobile phone - view later

More details

$22.56

$22.56 per 1

Key Features and Benefits

ABC Insulation Piercing Connector 35-35MM²

IPC (Insulation Piercing Connectors) are used to tap off low voltage XLPE insulated Aerial Bundled Cable (ABC), using a unique insulation piercing technique.

ABC IPC Features
Designed for all weather applications, corrosion resistant, ease of installation and low cost
• Connections can be made fully live in minutes, without time-consuming crimping, applying insulation or sealing compound
• Body moulded from tough, resilient, glass filled nylon for long service life exposed to weather (particularly sunlight) - rounded to prevent damage to adjacent conductors
• Extra hard aluminium contact teeth cut through insulation without splitting - ensure proper penetration into the conductor and electrical continuity without sacrificing mechanical strength of conductor
• Aluminium teeth ensure compatibility with aluminium conductor and will not deteriorate due to stress corrosion
• Rubber seals and grease prevent moisture entering cable for long term performance
• End caps provided are used to seal the end of the branch core
• Suitable for Aluminium and Copper

Instructions

IPC's are tightened onto the insulated conductor using a 13mm spanner and have a hex nut that shears once the correct torque is attained. The installation can be done fully live since the IPC is insulated and the insulation is not removed from the conductor. The contact pressure is maintained by the single hot dip galvanised bolt.

Technical Data

Conductive material
Aluminium teeth 99.6%
pure

Final metal state
Hard

Water proofing
Rubber seals and grease
6 kV withstand voltage test
in water

Temperature
Tested to 125°C
Conformant standards
AS4396
NF-C33020 (HN33S63) France
1000 heat cycles test to IEC 20
(sec. 256)
Designed for cable made to
AS 3560

Accepting authorities
Energy Australia
Integral Energy


Ordering Information

Part No. Main Cable
Range (mm²)
Branch Cable
Range (mm²)
Fastener
No. x Size
Fastener
A/F (mm)
Torque
(Nm)
IPC35/35 35-6 35-6 1 13 11
IPC95/6 Use IPC95/10 will accommodate 6mm
IPC95/10 95-6 10-1.5 1 13 11
IPC95/35 95-25 35-6 1 13 14
IPC95/95 150-16 95-16 1 13 16
IPC150/35 150-35 35-16 1 13 14
IPC150/95 Use IPC95/95 will accommodate 150mm